Troubleshooting Use the table below to solve minor Back-UPS ES installation or operation problems. Consult APC Online Technical Support or call APC Technical Support for assistance with problems that cannot be resolved using the table below. Back-UPS™ ES 550/700 Connect the Battery The Back-UPS is shipped with one battery cable disconnected. Remove the “Stop! Connect the Battery” label that covers the outlets. Prior to connecting any equipment to the unit, connect the battery cable to the unused battery terminal. It is normal for.
Type: (PDF)
Page
4
4
Jul 10, 2009 APCMODEL: Back-UPS ES 500 END APC: Mon Jul 06 10:44:01 EDT 2009 I am due for a larger UPS anyway, so I am upgrading to the APC BACK-UPS RS 1500VA LCD 120V. The user manual did not specify these indications as to being a partially dead battery. But it appears to be so.
If you get stuck in repairing a defective appliance download this repair information for help. See below.
Good luck to the repair!
Please do not offer the downloaded file for sell only use it for personal usage!
Looking for other manual?
Good luck to the repair!
Please do not offer the downloaded file for sell only use it for personal usage!
Looking for other manual?
APC ES 500 User Manual. Troubleshooting, Order replacement battery, Wall mounting template. APC Tools. Manuals Directory ManualsDir.com - online owner manuals library. The Back-UPS ES can only operate on battery power for a limited amount of time. The Back-UPS ES is overloaded. PowerChute Personal Edition software has performed a shutdown due to a power failure. The Back-UPS ES has exhausted its available battery power. Connected equipment does not accept the step-approximated sine waveform the Back-UPS ES. The Back-UPS ES may require service. The Back-UPS ES is using battery.
- If you have any question about repairing write your question to the Message board. For this no need registration.
- Please take a look at the below related repair forum topics. May be help you to repair.
Warning!
If you are not familiar with electronics, do not attempt to repair!
You could suffer a fatal electrical shock! Instead, contact your nearest service center!
Note! To open downloaded files you need acrobat reader or similar pdf reader program. In addition, some files are archived,If you are not familiar with electronics, do not attempt to repair!
You could suffer a fatal electrical shock! Instead, contact your nearest service center!
so you need WinZip or WinRar to open that files. Also some files are djvu so you need djvu viewer to open them.
These free programs can be found on this page: needed progs
If you use opera you have to disable opera turbo function to download file!
If you cannot download this file, try it with CHROME or FIREFOX browser.
Sziasztok! Aki csinált már ilyet kérem segítsen, mert kifogytam az ötletekből. Régebben építettem Siemens telefonnal +PIC-el riasztót. Mivel már nem nagyon van ilyen öreg telefon vásároltam az ebay-on ilyeneket: Mivel 3,3V-on működik építette hozzá MAX3232-ből soros szintáttevőt. Sajnos semmiképpen nem tudom szóra bírni :-( A leírás szerint autobaud-ra van állítva, de én már próbáltam indenféle bitrátával 1200-115200-ig, de sajnos sehol nem biztos a kapcsolat. Ráadásul ha a terminálból AT parancsot küldök ki arra OK-t kellene válaszolnia, de ehelyett ö papagáj módra visszaküldi az AT parancsot OK nélkül. Ha azt írom be almafa, akkor ezt küldi vissza. Az analóg része működik, fel tudom hívni, és a rajta lévő LED-en látom is hogy hívom. Ha a MAX3232 ki-bemenetét rövidre zárom, hibátlanul működik. Már a vásárolt hardwarere is gondoltam, de kicsi a valódszínűsége, hogy mindhárom ugyan úgy hibás. Biztos, hogy én vagyok a láma, de nem jövök rá miért.
Üdvözletem mindenkinek. Vettem egy XBOX 360 Fat konzolt. A probléma az,hogy a front panelen lévő nyomógombbal nem kapcsol be. Az Eject gomb megnyomására bekapcsol. Utána a karon lévő középső gomb hosszas nyomásakor bekapcsol,de ha a táp ki volt húzva,utána vissza,azzal sem,csak Eject-tel. Kikapcsolni csak menüből lehet,a frontpanel kikapcsolást sem végez. Próbáltam két másik,tuti működő frontpanellel is,de arra sem reagál. Olvastam valahol,hogy North Bridge probléma lehet,de csak a South Bridge-ről van konkrét leírás,hol van. Tehát a kérdésem az,mi lehet a hiba oka és ha North Bridge,akkor az hol van. Üdvözlet:Tomszojer
Sziasztok Valakinek meg lenne a kapcsolási rajza az utókeringető panelről? U2008B ic van benne. Köszi Üdv Szabi
szervusztok Cryptobox 500HD mini nem kapcsol be,talan frissitesnel keletkezett a hiba...na mindegy. Szoval RS232 portrol sem lehet programmozni,feltehetoen bootloader tartomany hiba.A neten talaltam egy SPI mentest,aminek a beirasa utan,ahogy irtak,vminek a keszulek nem kap MAC cimet,ez igy is van. Az lenne a keresem,volna e Nektek ehhez a keszulekhez SPI flash tartalom? winbond 25Q64FVSIG a keszulek chassisa GS4201BF koszonom
If you want to join us and get repairing help please sign in or sign up by completing a simple electrical test
or write your question to the Message board without registration.
You can write in English language into the forum (not only in Hungarian)!
or write your question to the Message board without registration.
You can write in English language into the forum (not only in Hungarian)!
Advertising
Troubleshooting
Use the table below to solve minor Back-UPS ES installation or operation problems. Consult APC Online Technical Support or call APC
Technical Support for assistance with problems that cannot be resolved using the table below:
Technical Support for assistance with problems that cannot be resolved using the table below:
Back-UPS ES will not turn on.
No power available at the Surge Protection
outlets.
outlets.
Connected equipment loses power.
The Power On indicator is lit and the Back-
UPS ES is beeping four times every 30
seconds.
seconds.
The Power On indicator flashes once per
second and the Back-UPS ES beeps once
per second at the same time.
second and the Back-UPS ES beeps once
per second at the same time.
Building Wiring Fault indicator is lit.
Inadequate runtime.
Battery is disconnected and utility power is not available at
the wall outlet.
the wall outlet.
Surge Protection outlets have been overloaded.
Utility power not available at the wall outlet.
Equipment is connected to the “Surge Protection” outlets.
The Back-UPS ES is overloaded.
PowerChute Personal Edition software has performed a
shutdown due to a power failure.
The Back-UPS ES has exhausted its available battery
power.
power.
Connected equipment does not accept the step-
approximated sine waveform the Back-UPS ES.
The Back-UPS ES may require service.
The Back-UPS ES is using battery.
Battery capacity is low (about 2 minutes of use remaining).
Your building wiring presents a shock hazard. Using the
Back-UPS with this condition will void the warranty.
Back-UPS with this condition will void the warranty.
The battery is not fully charged.
Battery is near the end of useful life.
Connect the battery (see Connect Battery) and ensure power is available at the wall
outlet.
outlet.
Reduce the amount of equipment plugged into Surge Protection outlets.
Ensure that the fuse or circuit breaker for the outlet is not tripped, and that the wall
switch controlling the outlet (if any) is in the ON position.
Ensure that the equipment you want to stay powered during a power failure is
plugged into the “Battery Backup plus Surge Protection” outlets and NOT the “Surge
plugged into the “Battery Backup plus Surge Protection” outlets and NOT the “Surge
Protection” outlets.
Make sure that the equipment plugged into the outlets of the unit are not overloading
the capacity of the unit. Try removing some of the equipment and see if the problem
continues.
the capacity of the unit. Try removing some of the equipment and see if the problem
continues.
The Back-UPS ES is operating normally.
The Back-UPS ES can only operate on battery power for a limited amount of time.
The unit will eventually turn off when the available battery power has been used.
Allow the unit to recharge for 16 hours before continuing use of the unit.
The unit will eventually turn off when the available battery power has been used.
Allow the unit to recharge for 16 hours before continuing use of the unit.
The output waveform is designed for computers and computer-related equipment. It
is not designed for use with motor-type equipment.
Contact APC Technical Support for further troubleshooting.
The Back-UPS ES is operating normally and using battery power. Once On Battery,
you should save your current work, power down your equipment, and turn the unit
OFF. Once normal power is restored, you may turn the unit back ON and power
you should save your current work, power down your equipment, and turn the unit
OFF. Once normal power is restored, you may turn the unit back ON and power
your equipment.
The Back-UPS ES is about to shut off due to a low battery charge condition! When
the unit beeps once every second, the battery has about 2 minutes of power
remaining. Immediately power down your computer and turn the unit OFF. When
the unit beeps once every second, the battery has about 2 minutes of power
remaining. Immediately power down your computer and turn the unit OFF. When
normal power returns, the unit will recharge the battery.
Call a qualified electrician for service.
Allow the unit to charge by leaving it plugged into the wall at least 16 hours.
As a battery ages, the amount of runtime available will decrease. You can replace
the battery by ordering one at www.apc.com. Batteries also age prematurely if the
the battery by ordering one at www.apc.com. Batteries also age prematurely if the
Back-UPS ES is placed near excessive heat.
Problem
Probable Cause
Solution
Specifications
Warranty
Service
APC Contact Information
Input
Voltage
120 Vrms Nominal
Frequency
47 - 63 Hz
Brownout Transfer
96 Vrms, typical
Over-voltage Transfer
136 Vrms, typical
Output
UPS Capacity (3 outlets)
350 VA / 200 W 500 VA / 300 W
Surge Capacity (6 outlets)
12 Amps (including UPS output)
Voltage
On Battery
On Battery
115 Vrms + 8%
(step-approximated sine wave)
Frequency - On Battery
50-60 Hz + 1 Hz
Transfer Time
5 ms typical, 8 ms maximum
Protection and Filter AC Surge Protection
Full time, 375 joules
Telephone Surge Protection
Single line (2-wire)
EMI/RFI Filter
Full time
AC Input
Resettable circuit breaker
Battery
Type
Sealed, maintenance-free lead acid
Average Life
2 - 4 years depending on the number of discharge
cycles and environmental temperature
Physical
Net Weight
9.20 lb. (4.18 kg.) 13.25 lb. (6.02 kg.)
Size
3.3” (H) x 10.9” (W) x 6.9” (D)
(8.3 x 27.8 x 17.5 cm)
Operating Temperature
+32
o
F to 104
o
F (0
o
C to 40
o
C)
Storage Temperature
+ 5
o
F to 113
o
F (-15
o
C to 45
o
C)
Operating Relative Humidity
0 to 95% non-condensing
Operating Elevation
0 to 10,000 ft (0 to 3,000m)
Safety/Regulatory
Safety Approvals
UL 1778 listed, cUL certified per
CSA standard C22.2 No. 107.1
EMC Compliance
FCC part 68, FCC part 15 Class B
Notice: This device complies with part 15 of
the FCC rules. Operation is subject to the
following two conditions: (1) This device may
not cause harmful interference, and (2) This
device must accept any interference received,
including interference that may cause
undesired operation.
the FCC rules. Operation is subject to the
following two conditions: (1) This device may
not cause harmful interference, and (2) This
device must accept any interference received,
including interference that may cause
undesired operation.
Model
BE350U
BE500U
The standard warranty is 2 years from the date of purchase. APC’s standard
procedure is to replace the original unit with a factory reconditioned unit. Customers
procedure is to replace the original unit with a factory reconditioned unit. Customers
who must have the original unit back due to assigned asset tags and set depreciation
schedules must declare such a need at first contact with APC Technical Support. APC
will ship the replacement unit once the defective unit is received by the repair
schedules must declare such a need at first contact with APC Technical Support. APC
will ship the replacement unit once the defective unit is received by the repair
department or cross-ship upon the provision of a valid credit card number. The
customer pays for shipping to APC, and APC pays ground freight transportation costs
back to the customer.
customer pays for shipping to APC, and APC pays ground freight transportation costs
back to the customer.
Please DO NOT RETURN Back-UPS ES to the place of purchase under any
circumstances.
circumstances.
1. Consult the Troubleshooting section to eliminate common problems.
2. Verify the battery is connected (see Connect Battery) and that the Circuit Breaker is
not tripped (see Troubleshooting section).
not tripped (see Troubleshooting section).
If you still have problems or questions, please contact APC via the internet or at one of
the phone numbers listed below.
the phone numbers listed below.
3. Before contacting APC, please be sure to record the date purchased, UPS model,
and serial number (on bottom of unit).
and serial number (on bottom of unit).
4. Be prepared to troubleshoot the problem over the telephone with a Technical
Support Representative. If this is not successful, the representative will issue a Return
Material Authorization Number (RMA#) and a shipping address.
Support Representative. If this is not successful, the representative will issue a Return
Material Authorization Number (RMA#) and a shipping address.
Pack the unit in its original packaging. If the original packaging is not available, ask
APC Technical Support about obtaining a new set. Pack the unit properly to avoid
APC Technical Support about obtaining a new set. Pack the unit properly to avoid
damage in transit. Never use foam beads for packaging. Damage sustained in transit
is not covered under warranty (insuring the package for full value is recommended).
is not covered under warranty (insuring the package for full value is recommended).
5. Write the RMA# on the outside of the package.
6. Return the unit by insured carrier to the address given to you by APC Technical
Support.
Online Technical Support . . . . . http://support.apc.com
Web Site . . . . . . . . . . . . . . . . . . . www.apc.com
USA/Canada . . . . . . . . . . . . . . . 1.800.800.4272
Mexico . . . . . . . . . . . . . . . . . . . . . +52.292.0253 / 52.292.0255
Brazil . . . . . . . . . . . . . . . . . . . . . . . +0800.12.72.1
Worldwide . . . . . . . . . . . . . . . . . +1.401.789.5735
Web Site . . . . . . . . . . . . . . . . . . . www.apc.com
USA/Canada . . . . . . . . . . . . . . . 1.800.800.4272
Mexico . . . . . . . . . . . . . . . . . . . . . +52.292.0253 / 52.292.0255
Brazil . . . . . . . . . . . . . . . . . . . . . . . +0800.12.72.1
Worldwide . . . . . . . . . . . . . . . . . +1.401.789.5735
Order Replacement Battery
Apc Back-ups Es 500 Service Manual
Replace with an APC qualified battery. Replacement batteries can be ordered from
www.apc.com (valid credit card required). Have your Back-UPS ES model number
www.apc.com (valid credit card required). Have your Back-UPS ES model number
available when ordering. Your model number can be found on the bottom of the unit.
Wall Mounting Template
7.08 in.
(180 mm)
Sold by:
Apc Ups Es 350 Manual
http://www.TWAcomm.com
Toll Free: (877) 892-2666
Toll Free: (877) 892-2666
Advertising
Apc Ups Es 500